SIEMENS V20 VFD DRIVE FAULTS CODE LIST PART-1
In this article we are going to discuss about siemens v20 vfd drive fault Cause and Remedy for this fault codes ( F1, F2 , F3 , F4 , F5 , F6 , F11 , F12 , F20 , F35 )
SIEMENS V20 DRIVE |
- Motor power (P0307) does not correspond to the inverter power (r0206).
- Motor lead short circuit
- Earth faults
- r0949 = 0: Hardware reported
- r0949 = 1: Software reported
- r0949 = 22: Hardware reported
REMEDY :
Check the following:
- Motor power (P0307) must correspond to inverter power (r0206).
- Cable length limits must not be exceeded.
- Motor cable and motor must have no short-circuits or earth faults.
- Motor parameters must match the motor in use.
- Value of stator resistance (P0350) must be correct.
- Motor must not be obstructed or overloaded.
- Increase ramp-up time (P1120)
- Reduce starting boost level (P1312)
- Main supply voltage too high
- Motor is in regenerative mode
- r0949 = 0: Hardware reported
- r0949 = 1 or 2: Software reported
REMEDY :
Check the following:
- Supply voltage (P0210) must lie within limits indicated on rating plate.
- Ramp-down time (P1121) must match inertia of load.
- Required braking power must lie within specified limits.
- Vdc controller must be
enabled (P1240) and parameterized properly.
- Regenerative mode can be caused by fast ramp downs or if the motor is driven by an active load.
- Higher inertia requires longer
ramp times; otherwise, apply braking resistor.
F3 - FAULT: Undervoltage
CAUSE :
- Main supply failed.
- Shock load outside specified limits.
- r0949 = 0: Hardware reported
- r0949 = 1 or 2: Software reported
- Inverter overloaded
- Ventilation inadequate
- Pulse frequency too high
- Surrounding temperature too high
- Fan inoperative
REMEDY :
Check the following:
- Load or load cycle too high?
- Motor power (P0307) must match inverter power (r0206)
- Pulse frequency must be set to default value
- Surrounding temperature too high?
- Fan must turn when inverter is running
F5 - FAULT: Inverter I2t
CAUSE :
- Inverter overloaded.
- Load cycle too demanding.
- Motor power (P0307) exceeds inverter
- power capability (r0206).
REMEDY :
Check the following:
- Load cycle must lie within specified limits.
- Motor power (P0307) must match inverter power (r0206)
Note :
- F5 cannot be cleared until the inverter overload
utilization (r0036) is lower
than the inverter I2t warning (P0294).
F6 - FAULT: Chip Temperature Rise Exceeds Critical Levels
CAUSE :
- Load at start-up is too high
- Load step is too high
- Ramp-up rate is too fast
REMEDY :
Check the following:
- Load or load step too high?
- Increase ramp-up time (P1120).
- Motor power (P0307) must match inverter power (r0206).
- Use setting P0290 = 0 or 2 for preventing F6.
F11 - FAULT: Motor over Temperature
CAUSE :
- Motor overloaded
- This fault may occur if small motors (≤ 250 W, 4- or 2-pole) are used and run at a frequency below 15 Hz, even though the motor temperature is within limits.
REMEDY :
Check the following:
- Load or load step too high?
- Motor nominal over temperatures (P0626 - P0628) must be correct
- Motor temperature warning level (P0604) must Match
- Motor current is not in excess of the motor nominal current as indicated by the motor rating plate
- Physical temperature of the motor lies within limits
- If these two conditions are
satisfied, then set parameter P0335 = 1.
F12 - FAULT: Inverter Temperature Signal Lost
CAUSE :
- Wire breakage of inverter temperature (heat sink) sensor.
F20 - FAULT: DC Ripple Too High
CAUSE :
- The calculated DC ripple level has exceeded the safe threshold.
- This is commonly caused by loss of one of the mains input phases.
REMEDY :
- Check the mains supply wiring.
F35 - FAULT: Maximum number of auto restart attempts exceeded
CAUSE :
- Auto restart attempts exceed value of P1211.