Danfoss VLT micro drive FC 51 Name Plate
In this Article, we are going to discuss about what specifications are mentioned on the Danfoss VLT micro drive FC 51 name plate sticker.
Welcome to controls and systems blog page,
- The nameplate sticker is located on the top of each VFD drives and shows the ratings, serial number, warnings catalog number, and other relevant data for each unit.
- This nameplate sticker is mostly the same in the VLT model VFD drives, with only a few changes in the some VLT model VFD drives.
1st ROW: (TYPE CODE)
Position
1 - 3 [FC]- is Product group,
Possible choice is: Frequency converters,
Position 4 - 6 [051] is Series and product type,
Possible choice is: Micro Drive,
Position 7 - 10 [P] is Power size,
Possible choice is: 0.18 to 22 kilo watt.
Position 11 - 12 [S2] is Mains voltage,
Possible
choice is:
- S2 that means Single phase 200 to 240 Volt AC,
- T2 that means 3-phase, 200 to 240 Volt AC,
- T4 that means 3-phase, 380 to 480 Volt AC,
Position 13 - 15 [E20] is Enclosure,
Possible
choice is: IP20/Chassis,
Position 16 - 17 [H3] is RFI filter,
Possible choice is:
- HX - that means No RFI filter,
- H1 - that means RFI filter class A1/B,
- H3 - that means RFI filter A1/B reduced cable length 1,
Position 18 [X] is Brake,
Possible
choice is:
- B - that means Brake chopper included (from 1.5 kilo watt and up),
- X - that means No brake chopper included.
Position 19 [X] is Display,
Possible
choice is:
- X - that means No Local Control Panel,
- N - that means Numerical Local Control Panel,
- P - that means Numerical Local Control Panel with potentiometer,
Position 20 [C] is Coating PCB,
Possible
choice is:
- C - that means Coated PCB,
- X - that means No coated PCB,
Position 21 [X] is Mains option,
Possible
choice is No mains option,
Position 22 [X] is Adaptation A,
Possible choice is No adaptation,
Position 23 [X] is Adaptation B,
Possible choice is No adaptation,
Position 24 - 27 [SXXX] is Software release,
Possible
choice is Latest release - standard software,
2nd ROW:
P/N 132F0002 is the drive code
number.
S/N:000000G416 is the drive serial number.
The last 3 digits Indicate the week and year that the unit was built, for (e.g) 416,
41 is week
and 6 is year that means 2016,
3rd ROW:
0.37 kW 0.5 HP is the
drive Power rating.
4th ROW:
IN: 1x200-240V 50/60Hz 6.1A
is the drive input voltage, frequency and current,
5th ROW:
OUT: 3x0-Vin 0-400Hz 2.2A is the drive output voltage, frequency and
current.
6th ROW:
CHASSIS I IP20 Temp. 40°C/104°F is the drive chassis IP rating and drive
Temperature.
SYNBOLS:
The 1st
symbol is representing CE conformity.
The 2nd
symbol is representing Restriction of Hazardous
Substances.
The 3rd
symbol is representing Underwriters Laboratories.
The 4th
symbol is representing CAUTION:
Below the caution, it is mentioned to refer to the drive manual.
The 5th
symbol is representing WARNING:
Below the warning is an indication of the discharge time.
The 6th symbol is representing Disposal instruction:
- Equipment containing electrical components must not be disposed of together with domestic waste.
- It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
Note:
Removing
the labels from the VLT Common AC Drive Modules can result in loss of warranty
Related Video Link:
What Specifications are Mentioned on the Danfoss VLT Micro Drive FC 51 name plate sticker: https://youtu.be/iRyk_L-C57I
Danfoss VFD Drive LCP SIMULATOR SoftwareTool Download Link:
Social Media Link:
Will i hope this Article is useful to you, thank you for Visiting our Blog, Have a great day.