DANFOSS FC-302/301 VFD DRIVE PARAMETER SETTINGS PART-2

DANFOSS FC-304/302/301 VFD DRIVE PARAMETER SETTINGS PART-2

60 Hp Danfoss FC-301 Drive



This Parameter Setting is Suitable for Manual ON/OFF Mode with using External START / STOP Push Button , External RESET and Pot meter mode.



DANFOSS FC-304 VFD DRIVE PARAMETER LIST 

Parameter

Setting

Description

0-02

1

Motor Speed Unit (Hz)

1-20

22 kw

Motor Kilowatt

1-21

18 HP

Motor HP

1-22

415 Volt

Motor Voltage

1-23

50 Hz

Motor Frequency

1-24

23 Amps

Motor Current

1-25

1450 Rpm

Motor Speed

3-00

0

Min - Max

3-01

3

HZ

3-02

0 Hz

Min Reference

3-03

50 Hz

Max Reference

3-04

[0] Sum

Reference Function

3-10

[0] 0.00 %

Preset Reference

3-11

5.0 Hz

Jog Speed [Hz]

3-12

0.00 %

Catch up/slow Down Value

3-13

0

Linked to Hand / Auto

3-14

0.00 %

Preset Relative Reference

3-15

1

Reference Resource 1 (Analog Input 53)

3-16

20

Reference Resource 2 (Digital pot meter)

3-17

11

Reference Resource 3 (Local Bus Reference)

3-18

[0] No function

Relative scaling Reference Resource

3-41

30 s

Ramp Up

3-42

30 s

Ramp Down

4-12

0.0 Hz

Motor speed limit low

4-14

50 Hz

Motor speed limit High

5-00

[0] PNP

Digital I/O mode

5-01

[0] Input

Terminal 27 mode

5-10

[8] Start

Terminal 18 Digital Input

5-11

[10] Reversing

Terminal 19 Digital Input

5-12

[2] Cost Inverse

Terminal 27 Digital Input

5-14

[1] Reset

Terminal 32 Digital Input (External PB)

5-15

[0] No function

Terminal 33 Digital Input

5-40

10 (Alarm)

Function Relay

5-41

0.01 S

ON Delay Relay

5-42

0.01 S

OFF Delay Relay

6-10

0.0 v

Terminal 53 Low Voltage

6-11

10.0 v

Terminal  53 High Voltage

6-14

30 Hz

Terminal 53 low ref / feed back

6-15

40 Hz

Terminal 53 High ref / feed back

8-50

2 (logic AND)

Costing

8-51

3 (Logic OR)

Quick stop

8-52

3 (Logic OR)

DC Brake

8-53

3 (Logic OR)

Start

8-54

3 (Logic OR)

Reversing

8-55

3 (Logic OR)

Set up select

8-56

3 (Logic OR)

Presence Ref Select

16-62

10.0

Analog Input (Actual reference Volt)

 

 

 

This Parameter Setting is Suitable for Manual ON/OFF Mode and Pot meter mode.

 

DANFOSS 301 TERMINAL CONNECTION :

Drive Port

Wire Port :

12 th Terminal Port is ( +24v OUT )
13 th Terminal  Port is ( +24v OUT )
27 th Terminal  Port is ( DIGITAL IN/OUT )
18 th Terminal  Port is ( DIGITAL INPUT)
32 th Terminal  Port is ( DIGITAL INPUT)
50 th Terminal  Port is ( +10v dc OUT )
53 th Terminal  Port is ( ANALOG INPUT )
55 th Terminal  Port is ( COM ANALOG INPUT )

Wire Connection :

  • Take out ( +24v OUTPUT ) from 12 th Terminal  Port and give to 18 th ( DIGITAL INPUT) Terminal  port also loop 12 and 27 Terminal  port , for the Purpose of  ON / OFF the VFD drive with External START,STOP Push Button.
  • Take out ( +24v OUTPUT ) from 13 th Terminal  Port and give to 32 ( DIGITAL INPUT) Terminal port , for the Purpose of  RESET the Alarm with External Push Button.
  • Take out ( +10v dc OUTPUT ) from 50 th Terminal  Port and give to POTMETER 1st terminal and Take out ( COM ANALOG INPUT ) from 55 th Terminal  Port and give to POTMETER 3rd terminal , finally Take Regulated Voltage from POTMETER 2nd terminal and give to Drive 53 ( ANALOG INPUT ) Terminal  Port.



 Factory Reset

To Reset the Danfoss Vfd Drive First ‘SWITCH OFF’ the Drive Main Power Supply. 

Then After ‘SWITCH ON ‘ the Drive Main Power Supply.Before Press ( Status + Menu + OK ) Button simultaneity after the Drive will Completely in Factory Reset Condition.