DANFOSS FC-302/301 VFD DRIVE PARAMETER SETTINGS PART-2
DANFOSS FC-304/302/301 VFD DRIVE PARAMETER SETTINGS PART-2
DANFOSS FC-304 VFD DRIVE PARAMETER LIST |
||
Parameter |
Setting |
Description |
0-02 |
1 |
Motor Speed Unit (Hz) |
1-20 |
22 kw |
Motor
Kilowatt |
1-21 |
18 HP |
Motor HP |
1-22 |
415 Volt |
Motor
Voltage |
1-23 |
50 Hz |
Motor
Frequency |
1-24 |
23 Amps |
Motor
Current |
1-25 |
1450 Rpm |
Motor Speed |
3-00 |
0 |
Min - Max |
3-01 |
3 |
HZ |
3-02 |
0 Hz |
Min
Reference |
3-03 |
50 Hz |
Max
Reference |
3-04 |
[0] Sum |
Reference Function |
3-10 |
[0] 0.00 % |
Preset Reference |
3-11 |
5.0 Hz |
Jog Speed [Hz] |
3-12 |
0.00 % |
Catch up/slow Down Value |
3-13 |
0 |
Linked to
Hand / Auto |
3-14 |
0.00 % |
Preset
Relative Reference |
3-15 |
1 |
Reference
Resource 1 (Analog Input 53) |
3-16 |
20 |
Reference
Resource 2 (Digital pot meter) |
3-17 |
11 |
Reference
Resource 3 (Local Bus Reference) |
3-18 |
[0] No function |
Relative
scaling Reference Resource |
3-41 |
30 s |
Ramp Up |
3-42 |
30 s |
Ramp Down |
4-12 |
0.0 Hz |
Motor speed
limit low |
4-14 |
50 Hz |
Motor speed
limit High |
5-00 |
[0] PNP |
Digital I/O
mode |
5-01 |
[0] Input |
Terminal 27
mode |
5-10 |
[8] Start |
Terminal 18
Digital Input |
5-11 |
[10] Reversing |
Terminal 19
Digital Input |
5-12 |
[2] Cost Inverse |
Terminal 27
Digital Input |
5-14 |
[1] Reset |
Terminal 32
Digital Input (External PB) |
5-15 |
[0] No function |
Terminal 33
Digital Input |
5-40 |
10 (Alarm) |
Function
Relay |
5-41 |
0.01 S |
ON Delay
Relay |
5-42 |
0.01 S |
OFF Delay
Relay |
6-10 |
0.0 v |
Terminal 53
Low Voltage |
6-11 |
10.0 v |
Terminal 53 High Voltage |
6-14 |
30 Hz |
Terminal 53
low ref / feed back |
6-15 |
40 Hz |
Terminal 53
High ref / feed back |
8-50 |
2 (logic AND) |
Costing |
8-51 |
3 (Logic OR) |
Quick stop |
8-52 |
3 (Logic OR) |
DC Brake |
8-53 |
3 (Logic OR) |
Start |
8-54 |
3 (Logic OR) |
Reversing |
8-55 |
3 (Logic OR) |
Set up
select |
8-56 |
3 (Logic OR) |
Presence Ref
Select |
16-62 |
10.0 |
Analog Input
(Actual reference Volt) |
|
|
|
This
Parameter Setting is Suitable for Manual ON/OFF Mode and Pot meter mode. |
DANFOSS 301
TERMINAL CONNECTION :
Drive Port |
Wire Port :
Wire Connection :
- Take out ( +24v OUTPUT ) from 12 th Terminal Port and give to 18 th ( DIGITAL INPUT) Terminal port also loop 12 and 27 Terminal port , for the Purpose of ON / OFF the VFD drive with External START,STOP Push Button.
- Take out ( +24v OUTPUT ) from 13 th Terminal Port and give to 32 ( DIGITAL INPUT) Terminal port , for the Purpose of RESET the Alarm with External Push Button.
- Take out ( +10v dc OUTPUT ) from 50 th Terminal Port and give to POTMETER 1st terminal and Take out ( COM ANALOG INPUT ) from 55 th Terminal Port and give to POTMETER 3rd terminal , finally Take Regulated Voltage from POTMETER 2nd terminal and give to Drive 53 ( ANALOG INPUT ) Terminal Port.
Use full information
ReplyDeleteThank u for your response...
DeleteUseful information
ReplyDeleteuseful content
ReplyDeleteUseful
ReplyDeleteUpload more useful information
ReplyDeleteGood Way to know other drive settings and parameters
ReplyDeleteThank you for this post
ReplyDeleteEffective information
ReplyDeleteValuable information
ReplyDeleteThank you for sharing this setting ..very useful
ReplyDeleteGood
ReplyDeleteUseful
ReplyDeleteThanks for this topics very useful information
ReplyDeleteWow very useful information
ReplyDelete