Parameter

Setting

Description

1-20

22 kw

Motor Kilowatt

1-21

18 HP

Motor HP

1-22

415 Volt

Motor Voltage

1-23

50 Hz

Motor Frequency

1-24

23 Amps

Motor Current

1-25

1450 Rpm

Motor Speed

3-00

0

Min - Max

3-01

3

HZ

3-02

0 Hz

Min Reference

3-03

50 Hz

Max Reference

3-04

Reference Function

 

3-12

No Operation

 

3-13

0

Linked to Hand / Auto

3-14

50 Hz

 

3-15

1

Reference Resource (Analog Input 53)

3-41

30 s

Ramp Up

3-42

30 s

Ramp Down

4-12

0.0 Hz

Motor speed limit low

4-14

50 Hz

Motor speed limit High

5-40

5

Function Relay (Drive Running)

6-10

0.0 v

53 Low Voltage

6-11

10.0 v

53 High Voltage

6-14

30 Hz

Terminal 53 low ref / feed back

6-15

40 Hz

Terminal 53 High ref / feed back

8-50

2 (logic AND)

Costing

8-51

3 (Logic OR)

Quick stop

8-52

3 (Logic OR)

DC Brake

8-53

3 (Logic OR)

Start

8-54

3 (Logic OR)

Reversing

8-55

3 (Logic OR)

Set up select

8-56

3 (Logic OR)

Presence Ref Select

 

 

 

 

 

 

 

 

 

This Parameter Setting is Suitable for Manual ON/OFF Mode , Auto Frequency Mode , its Deepened on (0-10)v Dc signal.

 

DANFOSS 301 , 304 TERMINAL CONNECTION

 




To Reset the Danfoss Vfd Drive First ‘SWITCH OFF’ the Drive Main Power Supply. Then After ‘SWITCH ON ‘ the Drive Main Power Supply
Before Press ( Status + Menu + OK ) Button simultaneity after the Drive will Completely in Factory Reset Condition.



VIDEO LINK

DANFOSS INVERTER FC-301 / 302 Setting Parameters (Part-3)

DANFOSS INVERTER FC-301 / 302 Setting Parameters (Part-2)

DANFOSS INVERTER FC-301 / 302 Setting Parameters (Part-1)






Comments

Post a Comment

Popular posts from this blog

Danfoss VLT micro drive FC 51 Name Plate

QElectro Tech Software Overview

SIEMENS V20 VFD DRIVE MAIN PARAMETERS LIST

SIEMENS V20 VFD DRIVE FAULTS CODE LIST PART-1

SIEMENS VFD FAULTS CODE LIST PART-2