DANFOSS VLT 6000 VFD DRIVE PARAMETER LIST
DANFOSS VLT 6000 VFD DRIVE PARAMETER LIST
DANFOSS VLT 6000 VFD DRIVE PARAMETER LIST | ||
Parameter | Setting | Description |
012 | Disable | Hand Start Button |
013 | Enable | Auto Start Button |
102 | 15 KW | Motor Power |
103 | 415 V | Motor Voltage |
104 | 50 Hz | Motor Frequency |
105 | 28 A | Motor Current |
106 | 1450 Rpm | Motor Speed |
118 | 0.75 | Motor Power Factor |
200 | 0-120 Hz | Frequency Range |
201 | 0.0 Hz | Min Frequency |
202 | 50 Hz | Max Frequency |
203 | Linked to Hand / Auto | Reference site |
204 | 0 Hz | Min Reference |
205 | 50 Hz | Max Reference |
206 | 30 s | Ramp up Time |
207 | 30 s | Ramp Down Time |
210 | SUM | Ref. function |
300 | Reset | Digital Input 16 |
301 | Freeze Reference | Digital Input 17 |
302 | Start | Digital Input 18 |
303 | Reversing | Digital Input 19 |
304 | Coast Inverse | Digital Input 27 |
305 | Jog | Digital Input 29 |
306 | No Operation | Digital Input 32 |
307 | No Operation | Digital Input 33 |
308 | Reference | AI [V] Function |
309 | 0 v | AI 53 Scale Low |
310 | 10 v | AI 53 Scale High |
413 | 0 % | Min . Feedback |
414 | 100 % | Max . Feedback |
415 | % | Ref / Feedback unit |
416 | Liner | Feed back Con |
503 | Logic OR | Coasting |
504 | Logic OR | Dc Brake |
505 | Logic OR | Start |
506 | Digital Input | Reversing |
507 | Logic OR | Select. setup |
508 | Logic OR | Select Speed |
This Parameter Setting is Suitable for Manual ON/OFF , Mode , Auto Frequency Mode , its Deepened on (0-10)v Dc signal. |
DANFOSS VLT 6000 TERMINAL CONNECTION |