SIEMENS RWD 82,32 CONTROLLER PARAMETERS
In This Article we are going to see SIEMENS RWD (HVAC) Controller 82 , 32 Control Parameters.
RWD-82 |
Programming Screen
- PS 1 Parameter Setting Mode: Application No. Setup
- PS 2 Parameter Setting Mode: Defining Unit, X1 and X2
- PS 3 Parameter Setting Mode: Auxiliary Control
- PS 4 Parameter Setting Mode: Main Control Loop Setting
- PS Next To enter the next Parameter Setting
- PS Exit To exit the whole Parameter Setting Mode
Name |
Description |
Display,
Setting Range |
LIM ABS |
Absolute Limiter |
- |
WIN/SUM diG |
Winter/Summer
changeover by digital
input |
- |
Act |
Active
sensor input |
- |
LIM rEL |
Relative
Limiter |
- |
WIN/SUM AnLG |
Winter/Summer
changeover by analogue input |
- |
PS 2 - Unit, X1 & X2 sensor type and sensing range definition :
Name |
Description |
Display,
Setting Range |
UNT |
Unit
define |
°C, °F, % or
----(no unit display) |
X1LS |
X1 is Landis
& Staefa Ni 1000Ί temperature sensor |
Ni 1000Ί:
-50.150°C (unchangeable) |
X2LS |
X2 is Landis
& Staefa Ni 1000Ί temperature sensor |
Ni 1000Ί:
-50.150°C (unchangeable) |
X1Pt |
X1 is Platinum
Pt 1000Ί temperature sensor |
Pt 1000Ί:
-20.180°C (unchangeable) |
X2Pt |
X2 is Platinum
Pt 1000Ί temperature sensor |
Pt 1000Ί:
-20.180°C (unchangeable) |
X1
0-10 |
X1 is 0-10 Vdc
input sensor |
0-10 Vdc:
-100.8000 |
X2
0-10 |
X2 is 0-10 Vdc
input sensor |
0-10 Vdc:
-100.8000 |
ÎX1 |
Calibration
offset for X1 (Ni & Pt sensor only) |
-5.5 K or -9°F.9°F |
ÎX2 |
Calibration
offset for X2 (Ni & Pt sensor only) |
-5.5 K or -9°F.9°F |
X2
L |
Start point of
the X2 (for 0-10 Vdc
only) |
-100.8000 |
X1
H |
Stop point of
the X1 (for 0-10 Vdc
only) |
-100.8000 |
X2
H |
Stop point of
the X2 (for 0-10 Vdc
only) |
-100.8000 |
X2VR |
Variable
Resistor |
0.1000 Ί |
PS 3 - Auxiliary Control Loop Setup :
Name |
Description |
Display,
Setting Range |
XP-h |
Proportion
band for heating |
|
XP-c |
Proportion band
for cooling |
|
XP-r |
Proportion band
for reverse acting |
Active
input: 0.05.7300 |
XP-d |
Proportion band
for direct acting |
Active
input: 0.05.7300 |
TN-h |
Integral action
time for heating |
0.4096
sec |
TN-c |
Integral action
time for cooling |
0.4096 sec |
TN-r |
Integral action
time for reverse acting |
0.4096 sec |
TN-d |
Integral action
time for direct acting |
0.4096 sec |
T |
Time elapsed to
allow next winter/summer changeover (Q1
only) |
0.4096 sec |
|
Compensation shift (Start point, End point & Shift differential) |
- |
MAX |
Maximum Limiter |
-80.8000 |
MIN |
Minimum Limiter |
-100.7980 |
WIN |
Winter
changeover point |
-100.8000 |
SUM |
Summer
changeover point |
-100.8000 |
PS 4 - Main Control Loop Setup :
Name | Description | Display,
Setting Range |
T1 | Minimum
switch off time for Q1 | 0.255 sec |
T2 | Minimum switch
off time for Q2 | 0.255
sec |
TCYC | Cycle time of
the actuator | 1.255
sec |
ON | Dependent loop.
On point of Q1 as a % of total (Q1+Q2) SD | 0.100
% |
TN3P | I time for
3-point actuator | 0.4096
sec |
XP3P | P band 3-point
actuator | 0.05.7300
(Depends on the X1 setting range) |
SD | Switching
Differential | 0.05.7300 |