SIEMENS BACnet Commercial Thermostat RDY2000BN Parameter List
In This Article we are going to see SIEMENS BACnet Commercial Thermostat RDY2000BN Model Parameter List 101 to 911.
Sequence of Operation
Parameter |
Definition |
Default |
P101 |
System Type |
CO |
P102 |
Cooling Stages |
2 |
P103 |
Heating Stages |
2 |
P104 |
Aux Heating Stages |
0 |
P105 |
Fan Operation |
ELE |
P106 |
Reversing Value |
0 |
P107 |
Scheduler Days |
2 |
P109 |
Units |
F |
P110 |
Changeover |
YES |
P111 |
Changeover Deadband |
5°F (2.5 °C) |
P112 |
Daylight Savings |
NO |
P113 |
Display Temp Setpoint |
0 = Absolute |
Parameter 201 to 225
Parameter |
Definition |
Default |
P201 |
Heat Temp Limit |
95°F
(35.0 °C) |
P202 |
Cool Temp Limit |
50°F (10.0 °C) |
P203 |
Temperature Display Offset |
0°F (0 °C) |
P204 |
Override Time Limit |
2 |
P205 |
Override Temp Limit |
- |
P206 |
Heat
Pump Compressor Lock Out |
OFF |
P207 |
Heat
Pump Auxiliary Heat Lockout |
OFF |
P208 |
Service UV Lamp |
0 |
P209 |
Service Humidifier |
0 |
P210 |
Service Air Filter |
0 |
P211 |
Keypad Lockout |
OFF |
P212 |
Clock Format |
12 |
P213 |
Backlight |
15 |
P214 |
Humidity Display Offset |
0 |
P220 |
Heating Setpoint Comfort |
70 |
P221 |
Cooling Setpoint Comfort |
75 |
P222 |
Heating Setpoint Economy |
62 |
P223 |
Cooling Setpoint Economy |
82 |
P224 |
Heating Setpoint Protection |
40 |
P225 |
Cooling Setpoint Protection |
104 |
Parameter 301 to 320
Parameter |
Definition |
Default
|
P301 |
Configurable
Input 1 (IN 1) |
OFF |
P302 |
Temperature
Input 1 Type |
1 |
P303 |
Temperature
Input 1 Low |
0°F (-18.0 °C) |
P304 |
Temperature
Input 1 High |
120°F (50 °C) |
P305 |
Configurable
Input 2 (IN 2) |
OFF |
P306 |
Temperature
Input 2 Type |
1 |
P307 |
Temperature
Input 2 Low |
0°F (-18.0 °C) |
P308 |
Temperature
Input 2 High |
120°F (50 °C) |
P309 |
Configurable
Input 3 (IN 3) |
OFF |
P310 |
Temperature
Input 3 Type |
1 |
P311 |
Temperature
Input 3 Low |
0°F (-18.0 °C) |
P312 |
Temperature
Input 3 High |
120°F (50 °C) |
P313 |
Configurable
Input 4 (IN 4) |
OFF |
P314 |
Temperature
Input 4 Type |
1 |
P315 |
Temperature
Input 4 Low |
0°F (-18.0 °C) |
P316 |
Temperature
Input 4 High |
120°F (50 °C) |
P317 |
Aux
Output 1 (OUT 1) |
OFF |
P318 |
Aux
Output 2 (OUT 2) |
OFF |
P319 |
Aux
Output 3 (OUT 3 & C3) |
OFF |
P320 |
Independent
Humidity Control |
NO |
Parameter 401 to 407
Parameter |
Definition |
Default
|
P401 |
Unit
Number |
- |
P402 |
CO2
Setpoint |
1000 |
P403 |
Pre-Occupancy
Purge |
OFF |
P404 |
Occupancy Sensor Min Run Timer |
30 |
P405 |
Semi-Continuous
Fan |
ON |
P407 |
Installer
Password |
Current
PW |
Parameter 501 to 511
Parameter |
Definition |
Default
|
P501 |
Interstage
Delay Cooling |
5 |
P502 |
Interstage
Differential Cooling |
1°F (0.5 °C) |
P503 |
Cooling
Minimum Off Time |
5 |
P504 |
Cooling
Minimum On Time |
3 |
P505 |
Changeover
Delay |
10 |
P506 |
Cooling
Deadband |
1°F |
P507 |
Interstage
Delay Heating |
5 |
P508 |
Interstage
Differential Heating |
Conv
= 1°F
(0.5°C) HP = 2°F (1°C) |
P509 |
Heating
Minimum Off Time |
5 |
P510 |
Heating
Minimum On Time |
3
(10 if heat pump) |
P511 |
Heating
Deadband |
1°F (0.5 °C) |
Parameter 601 to 606 & 701,911
Parameter |
Definition |
Default
|
P601 |
MS/TP
MAC address |
255 |
P602 |
Baud
Rate |
A
= Auto |
P603 |
Device
Instance |
4194303 |
P604 |
Max
Master |
127 |
P605 |
Serial
number |
Display
only |
P606 |
Max
info frames |
1 |
|
||
P701 |
Firmware |
Display
only |
|
||
P911 |
Expert
Password |
Current
PW |