Siemens RDF300, 340,600 Room Thermostat Parameter List Part-1 (Service Level)

In This Article we are going to see Siemens RDF300, RDF340, RDF600 Room Thermostat Parameter List Part-1 Service Level.

Thermostat
SIEMENS RDF300

Control Parameter

Thermostat
Display


1. Operating mode selector / Protection.
2. Change fan operation
3. Adjust setpoint and control parameters


Siemens RDF300
Control Parameter



Parameter List

P01

Description : Control Sequence

Factory Setting : 

2-pipe, single duct [0 to 3] 1 (Cooling only)

4-pipe, [2 to 4] 4 (Heating & Cooling)

Setting Range :

0 = Heating only

1 = Cooling only

2 = Manual H or C

3 = Auto Changeover

4 = Heating & Cooling


P02

Description : Mode selection by user via operating mode button

Factory Setting : 1 (Protection, Comfort)

Setting Range :

1 = Protection, Comfort

2 = Protection, Comfort, Economy


P04

Description : Selection of °C or °F

Factory Setting : °C 

Setting Range : °C or °F


P05

Description : Sensor Calibration

Default Value : 0.0 K

Setting Range : -3 to +3 K


P06

Description : Standard Temperature display 

Default Value : 0 (Room Temp.)

Setting Range : 

0 = Room Temperature

1 = Setpoint


P07

Description : Additional user information 

Default Value : 0 (No Display)

Setting Range : 

0 = No display

1 = Temperature in °C / °F


P08

Description : Comfort basic Setpoint 

Default Value : 21 °C 

Setting Range : 5 to 40 °C 


P09

Description : Minimum Setpoint limitation in comfort  (W-Min comfort) 

Default Value : 5 °C 

Setting Range : 5 to 40 °C


P10

Description : Maximum Setpoint limitation in comfort  (W-Max comfort) 

Default Value : 35 °C 

Setting Range : 5 to 40 °C 


P11

Description : Setpoint of heating in Economy mode (W-heat Eco)

Default Value : 15 °C 

Setting Range : OFF, 5 °C W-cool Eco



P12

Description : Setpoint of cooling in Economy mode (W-cool Eco)

Default Value : 30 °C 

Setting Range : OFF, 40 °C W-heat Eco 


P13

Description : Electric heater in cooling mode 

Default Value : ON 

Setting Range : 

OFF = Disabled

ON = Enable


P14

Description : Button Lock (press operating mode button for 7 seconds to lock or unlock the button) 

Default Value : 0 (Disable)

Setting Range : 

0 = Disabled

1 = Auto Lock

2 = Manual Lock 

Comments