Siemens RDE100 Room Thermostat Parameter List

In This Article we are going to see SIEMENS Room Thermostat RDE100 model device Parameter List.


Overview :

SIEMENS RDE100  Thermostat mainly control for Room Temperature Heating Control Systems. its is used to control four (4) modes Comfort, Economy, Auto timer and Protection mode. The Siemens RDE Thermostat is available in two (2) model one is RDE100 Thermostat it is working in Main Power Supply AC 230 voltage and another one is RDE 100.1 Thermostat it is working in Battery Power supply DC 3 volt.


Operation and Settings :

Thermostat
RDE100


  1. Operating mode touch key
  2. Set
  3. OK
  4. Touch key for decreasing a value
  5. Touch key for increasing a value

Display :

Siemens RDE100 Room Thermostat
Display


Parameter List :


Parameter No : P01

Description : Time Format

Setting Range (default) : 

1 = 21:00 hours (default)

2 = 12:00 AM/PM


Parameter No : P02

Description : Selection of °C or °F

Setting Range (default) : 

1 = °C (default)

2 = °F


Parameter No : P03

Description : Standard temperature display

Setting Range (default) : 

1 = Room Temperature (default)

2 = Setpoint


Parameter No : P04

Description : Temperature sensor calibration

Setting Range (default) : -3 to +3 °C Step 0.5 °C (-6 to +6 °F, step 1 °F) Default: 0 °C


Parameter No : P06

Description : Comfort setpoint lock

Setting Range (default) : 

0 = OFF (default)

1 = ON  locked according to setting in permanent temperature setpoint.


Parameter No : P08

Description : Economy setpoint lock

Setting Range (default) : 

0 = OFF (default)

1 = ON  locked according to setting in permanent temperature setpoint.


Parameter No : P09

Description : Buzzer

Setting Range (default) : 

0 = OFF 

1 = ON (default)


Parameter No : P10

Description : Show frost protection icon

Setting Range (default) : 

0 = OFF (default) 

1 = ON


Parameter No : P11

Description : Time Switch type for Auto Timer

Setting Range (default) : 

0 = Individual Days (default)

1 = All 7 days

2 = 5/2 days


Parameter No : P12

Description : Periodic Pump Run

Setting Range (default) : 

0 = OFF (default) 

1 = ON

 

Parameter No : P14

Description : X1 External input (only for RDE100.1)

Setting Range (default) : 

0 = No input

1 = External sensor

2 = Digital Input


Note : 

  • If u Select 1 (External sensor) option means the Next Parameter P15 Setting Range is Automatically Enable the 0 = OFF (default) option.
  • If u Select 2 (Digital Input) option means the P17 parameter will Automatically Enabled.

 


Parameter No : P15

Description : Temperature limitation (only for RDE100.1)

Setting Range (default) : 

0 = OFF (default)

1 = ON


Note : 

  • If u Select 1 (ON) option means the Next Parameter P16 Setting Range is Automatically Enable the (25 to 60 °C, step 1 °C or 77 to 140 °F, step 1 °F ) option.



Parameter No : P16

Description : Maximum limitation temperature for underfloor heating (only for RDE100.1)

Setting Range (default) : 

25 to 60 °C, step 1 °C or

77 to 140 °F, step 1 °F

Default: 30 °C



Parameter No : P17

Description : Window contact features (only for RDE 100.1)

Setting Range (default) : 

0 = Normally Open Contact (default)

1 = Normally Closed Contact


Parameter No : P21

Description : Button scanning rate for the Capacitive buttons (RDE100.1 only)

Note: a shorter scanning rate means shorter battery life.

Setting Range (default) : 

0.2 = 0.25 s

0.5 = 0.5 s

1.0 = 1.0 s (default)

1.5 = 1.5 s


Parameter No : P22

Description : Reload factory settings

Setting Range (default) : 

0 = OFF (default)

1 = reload


Parameter No : P23

Description : Software version information

Setting Range (default) : No adjustment possible.


Parameter No : P78

Description : Control behavior

Setting Range (default) :

0 = On/Off, 1.0 K

1 = On/Off, 0.3 K

2 = TPI fast

3 = TPI medium

4 = TPI slow (default)


Parameter No : P89

Description : Forward shift on maximum

Setting Range (default) :

0, 0.5,…24 h

Default: 0 h


Parameter No : P90

Description : Early shutdown maximum

Setting Range (default) :

0, 0.5,…6 h

Default: 0 h


If you need more information about this Siemens RDE Room Thermostat please visit our YouTube Channel.