Siemens RDE100 Room Thermostat Parameter List
In This Article we are going to see SIEMENS Room Thermostat RDE100 model device Parameter List.
Overview :
SIEMENS RDE100 Thermostat mainly control for Room Temperature Heating Control Systems. its is used to control four (4) modes Comfort, Economy, Auto timer and Protection mode. The Siemens RDE Thermostat is available in two (2) model one is RDE100 Thermostat it is working in Main Power Supply AC 230 voltage and another one is RDE 100.1 Thermostat it is working in Battery Power supply DC 3 volt.
Operation and Settings :
- Operating mode touch key
- Set
- OK
- Touch key for decreasing a value
- Touch key for increasing a value
Display :
Parameter List :
Parameter No : P01
Description : Time Format
Setting Range (default) :
1 = 21:00 hours (default)
2 = 12:00 AM/PM
Parameter No : P02
Description : Selection of °C or °F
Setting Range (default) :
1 = °C (default)
2 = °F
Parameter No : P03
Description : Standard temperature display
Setting Range (default) :
1 = Room Temperature (default)
2 = Setpoint
Parameter No : P04
Description : Temperature sensor calibration
Setting Range (default) : -3 to +3 °C Step 0.5 °C (-6 to +6 °F, step 1 °F) Default: 0 °C
Parameter No : P06
Description : Comfort setpoint lock
Setting Range (default) :
0 = OFF (default)
1 = ON locked according to setting in permanent temperature setpoint.
Parameter No : P08
Description : Economy setpoint lock
Setting Range (default) :
0 = OFF (default)
1 = ON locked according to setting in permanent temperature setpoint.
Parameter No : P09
Description : Buzzer
Setting Range (default) :
0 = OFF
1 = ON (default)
Parameter No : P10
Description : Show frost protection icon
Setting Range (default) :
0 = OFF (default)
1 = ON
Parameter No : P11
Description : Time Switch type for Auto Timer
Setting Range (default) :
0 = Individual Days (default)
1 = All 7 days
2 = 5/2 days
Parameter No : P12
Description : Periodic Pump Run
Setting Range (default) :
0 = OFF (default)
1 = ON
Parameter No : P14
Description : X1 External input (only for RDE100.1)
Setting Range (default) :
0 = No input
1 = External sensor
2 = Digital Input
Note :
- If u Select 1 (External sensor) option means the Next Parameter P15 Setting Range is Automatically Enable the 0 = OFF (default) option.
- If u Select 2 (Digital Input) option means the P17 parameter will Automatically Enabled.
Parameter No : P15
Description : Temperature limitation (only for RDE100.1)
Setting Range (default) :
0 = OFF (default)
1 = ON
Note :
- If u Select 1 (ON) option means the Next Parameter P16 Setting Range is Automatically Enable the (25 to 60 °C, step 1 °C or 77 to 140 °F, step 1 °F ) option.
Description : Maximum limitation temperature for underfloor heating (only for RDE100.1)
Setting Range (default) :
25 to 60 °C, step 1 °C or
77 to 140 °F, step 1 °F
Default: 30 °C
Description : Window contact features (only for RDE 100.1)
Setting Range (default) :
0 = Normally Open Contact (default)
1 = Normally Closed Contact
Parameter No : P21
Description : Button scanning rate for the Capacitive buttons (RDE100.1 only)
Note: a shorter scanning rate means shorter battery life.
Setting Range (default) :
0.2 = 0.25 s
0.5 = 0.5 s
1.0 = 1.0 s (default)
1.5 = 1.5 s
Parameter No : P22
Description : Reload factory settings
Setting Range (default) :
0 = OFF (default)
1 = reload
Parameter No : P23
Description : Software version information
Setting Range (default) : No adjustment possible.
Parameter No : P78
Description : Control behavior
Setting Range (default) :
0 = On/Off, 1.0 K
1 = On/Off, 0.3 K
2 = TPI fast
3 = TPI medium
4 = TPI slow (default)
Parameter No : P89
Description : Forward shift on maximum
Setting Range (default) :
0, 0.5,…24 h
Default: 0 h
Parameter No : P90
Description : Early shutdown maximum
Setting Range (default) :
0, 0.5,…6 h
Default: 0 h