Siemens RDS110 Thermostat Parameter List Part-1

In This Article we are going to see SIEMENS RDS 110 THERMOSTAT Parameter List for (Multi-function inputs , Heating Setpoint , Humidification Setpoint , Dehumidification Setpoint , Function , Temperature Offset , Minimum Switchover Time Adjustment , and Other Settings ) 

Thermostat
RDS 110 Thermostat


Multi-Functional Inputs

Siemens Thermostat

NO : 1

Application Settings : X1 Room Temp.Ref at 0V

Descriptions : Room Temperature at 0V of the 0-10V input in terminal X1

Factory Settings : 0 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat  using terminal X1.


NO : 2

Application Settings : X1 Room Temp.Ref at 10V

Descriptions : Room Temperature at 10V of the 0-10V input in terminal X1

Factory Settings : 50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat using terminal X1


NO : 3

Application Settings : X2 Room Temp.Ref at 0V

Descriptions : Room Temperature at 0V of the 0-10V input in terminal X2

Factory Settings : 0 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat using terminal X2.


NO : 4

Application Settings : X2 Room Temp.Ref at 10V

Descriptions : Room Temperature at 10V of the 0-10V input in terminal X2

Factory Settings : 50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat using terminal X2.


NO : 5

Application Settings : Outside Temp.Ref at 0V

Descriptions : Outside air Temperature at 0V of the 0-10V input.

Factory Settings : -50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external outside air temperature sensor must be connected.


NO : 6

Application Settings : Outside Temp.Ref at 10V

Descriptions : Outside air Temperature at 10V of the 0-10V input.

Factory Settings : 80 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external outside air temperature sensor must be connected.


NO : 7

Application Settings : X1 Floor Temp.Ref at 0V

Descriptions : Floor Temperature at 0V of the 0-10V input in terminal X1.

Factory Settings : -50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X1.


NO : 8

Application Settings : X1 Floor Temp.Ref at 10V

Descriptions : Floor Temperature at 10V of the 0-10V input in terminal X1.

Factory Settings : 80 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X1.


NO : 9

Application Settings : X2 Floor Temp.Ref at 0V

Descriptions : Floor Temperature at 0V of the 0-10V input in terminal X2.

Factory Settings : -50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X2.


NO : 10

Application Settings : X2 Floor Temp.Ref at 10V

Descriptions : Floor Temperature at 10V of the 0-10V input in terminal X2.

Factory Settings : 80 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X2.



Heating Setpoint

temperature


NO : 11

Application Settings : Comfort Heating Setpoint

Descriptions : The default heating setpoint for Comfort defined in a Scheduler. This setpoint must be higher than that for Protection

Factory Settings : 21 °C

Range :  0 to 50 °C

Dependencies : N/A


NO : 12

Application Settings : Economy Heating Setpoint

Descriptions : The default heating setpoint for Economy defined in a Scheduler. This setpoint must be higher than that for Protection

Factory Settings : 19 °C

Range :  0 to 50 °C

Dependencies : N/A


NO : 13

Application Settings : Unoccupied Heating Setpoint

Descriptions : The default heating setpoint for Unoccupied mode. This setpoint must be higher than that for Protection

Factory Settings : 15 °C

Range :  0 to 50 °C

Dependencies : N/A


NO : 14

Application Settings : Protection Heating Setpoint

Descriptions : The default minimum heating setpoint to maintain when you switch the thermostat to OFF under operation Mode. 

Factory Settings : 7 °C

Range :  0 to 50 °C

Dependencies : This Setpoint is valid only if you keep the default Protection option for Application setting NO 37.


NO : 15

Application Settings : Maximum Heating Setpoint

Descriptions : The default maximum heating setpoint if the thermostat is not switched to OFF. If it is OFF, the maximum heating setpoint is then the heating protection setpoint.

Factory Settings : 35 °C

Range :  0 to 50 °C

Dependencies : The heating protection setpoint is valid only if you keep the default Protection option for Application setting NO 37.


In Next article we see balance Siemens RDS110 Thermostat Parameter List 