Siemens RDS110 Thermostat Parameter List Part-1

In This Article we are going to see SIEMENS RDS 110 THERMOSTAT Parameter List for (Multi-function inputs , Heating Setpoint , Humidification Setpoint , Dehumidification Setpoint , Function , Temperature Offset , Minimum Switchover Time Adjustment , and Other Settings ) 

Thermostat
RDS 110 Thermostat


Multi-Functional Inputs

Siemens Thermostat

NO : 1

Application Settings : X1 Room Temp.Ref at 0V

Descriptions : Room Temperature at 0V of the 0-10V input in terminal X1

Factory Settings : 0 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat  using terminal X1.


NO : 2

Application Settings : X1 Room Temp.Ref at 10V

Descriptions : Room Temperature at 10V of the 0-10V input in terminal X1

Factory Settings : 50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat using terminal X1


NO : 3

Application Settings : X2 Room Temp.Ref at 0V

Descriptions : Room Temperature at 0V of the 0-10V input in terminal X2

Factory Settings : 0 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat using terminal X2.


NO : 4

Application Settings : X2 Room Temp.Ref at 10V

Descriptions : Room Temperature at 10V of the 0-10V input in terminal X2

Factory Settings : 50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external room temperature sensor must be connected with the thermostat using terminal X2.


NO : 5

Application Settings : Outside Temp.Ref at 0V

Descriptions : Outside air Temperature at 0V of the 0-10V input.

Factory Settings : -50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external outside air temperature sensor must be connected.


NO : 6

Application Settings : Outside Temp.Ref at 10V

Descriptions : Outside air Temperature at 10V of the 0-10V input.

Factory Settings : 80 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external outside air temperature sensor must be connected.


NO : 7

Application Settings : X1 Floor Temp.Ref at 0V

Descriptions : Floor Temperature at 0V of the 0-10V input in terminal X1.

Factory Settings : -50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X1.


NO : 8

Application Settings : X1 Floor Temp.Ref at 10V

Descriptions : Floor Temperature at 10V of the 0-10V input in terminal X1.

Factory Settings : 80 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X1.


NO : 9

Application Settings : X2 Floor Temp.Ref at 0V

Descriptions : Floor Temperature at 0V of the 0-10V input in terminal X2.

Factory Settings : -50 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X2.


NO : 10

Application Settings : X2 Floor Temp.Ref at 10V

Descriptions : Floor Temperature at 10V of the 0-10V input in terminal X2.

Factory Settings : 80 °C

Range :  -50 to 80 °C

Dependencies : A DC 0-10V external floor temperature sensor must be connected using terminal X2.



Heating Setpoint

temperature


NO : 11

Application Settings : Comfort Heating Setpoint

Descriptions : The default heating setpoint for Comfort defined in a Scheduler. This setpoint must be higher than that for Protection

Factory Settings : 21 °C

Range :  0 to 50 °C

Dependencies : N/A


NO : 12

Application Settings : Economy Heating Setpoint

Descriptions : The default heating setpoint for Economy defined in a Scheduler. This setpoint must be higher than that for Protection

Factory Settings : 19 °C

Range :  0 to 50 °C

Dependencies : N/A


NO : 13

Application Settings : Unoccupied Heating Setpoint

Descriptions : The default heating setpoint for Unoccupied mode. This setpoint must be higher than that for Protection

Factory Settings : 15 °C

Range :  0 to 50 °C

Dependencies : N/A


NO : 14

Application Settings : Protection Heating Setpoint

Descriptions : The default minimum heating setpoint to maintain when you switch the thermostat to OFF under operation Mode. 

Factory Settings : 7 °C

Range :  0 to 50 °C

Dependencies : This Setpoint is valid only if you keep the default Protection option for Application setting NO 37.


NO : 15

Application Settings : Maximum Heating Setpoint

Descriptions : The default maximum heating setpoint if the thermostat is not switched to OFF. If it is OFF, the maximum heating setpoint is then the heating protection setpoint.

Factory Settings : 35 °C

Range :  0 to 50 °C

Dependencies : The heating protection setpoint is valid only if you keep the default Protection option for Application setting NO 37.


In Next article we see balance Siemens RDS110 Thermostat Parameter List 


Video Link : Siemens Smart Thermostat (RDS110) Technical Details Only Part 1

Comments

Popular posts from this blog

QElectro Tech Software Overview

Danfoss VLT micro drive FC 51 Name Plate

SIEMENS V20 VFD DRIVE FAULTS CODE LIST PART-1

SIEMENS V20 VFD DRIVE MAIN PARAMETERS LIST

Siemens RDG400KN Thermostat Parameter List