Schneider Altivar ATV-310 VFD Drive fault code Part-1

In this Article we are going to see Schneider Altivar ATV-310 VFD Drive Fault code, Possible Causes & Remedy Part-1,


Schneider
Schneider Altivar ATV-310 VFD



Code: F001 Pre Charge.

Schneider Altivar

Possible causes: Charging relay control fault or charging resistor damaged.

Remedy:

  • Turn the drive off and then back on again,
  • Check the connections,
  • Check the stability of the main supply,
  • Contact local Schneider Electric representative.

 

Code: F002 Unknown Drive Rating.

Schneider Altivar

Possible causes: Power card and stored card versions different.

Remedy: Contact local Schneider Electric representative.

 

Code: F003 Unknown or Incompatible Power Board.

Schneider Altivar

Possible causes: The power card is incompatible with the control card.

Remedy: Contact local Schneider Electric representative.

 

Code: F004 Internal Serial Link Fault.

Schneider Altivar

Possible causes: Communication interruption between the internal cards.

Remedy: Contact local Schneider Electric representative.

 

Code: F005 Invalid industrialization zone.

Schneider Altivar

Possible causes: Internal data inconsistent.

Remedy: Contact local Schneider Electric representative,

 

Code: F006 Current Measurement Circuit.

Schneider Altivar

Possible causes: Current measurement is not correct due to hardware circuit fault.

Remedy: Contact local Schneider Electric representative.

 

Code: ---- Problem with Application Firmware.

Schneider Altivar

Possible causes: Invalid application firmware update using the Multi-Loader tool,

Remedy: Re-download application firmware,

 

Code: F007 Internal Thermal Sensor Detected Fault.

Schneider Altivar

Possible causes: 

  • The drive temperature sensor is not operating correctly,
  • The drive is in short circuit or open,

Remedy: Contact local Schneider Electric representative.

 

Code: F008 Internal CPU

Schneider Altivar

Possible causes: Internal microprocessor fault,

Remedy: 

  • Turn the drive off and then back on again,
  • Contact local Schneider Electric representative.

 

Code: F009 Over Braking

Schneider Altivar

Possible causes: Sudden braking or load inertia too high.

Remedy:

  • Increase the deceleration time.
  • Install a module unit with a braking resistor if necessary.
  • Check the main supply voltage to ensure it is under the maximum acceptable (20% over maximum main supply during run status).

 

Code: F010 Over Current,

Schneider Altivar

Possible causes:

  • Parameters in the Motor control menu 300 are not correct,
  • Inertia or load too high,
  • Mechanical locking.

Remedy:

  • Check the parameters,
  • Check the size of the motor, drive, load,
  • Check the state of the mechanism.
  • Connect line motor chokes,
  • Reduce the Switching frequency range 315,
  • Check the ground connection of drive, motor cable and motor Insolation.

 

Code: F011 Drive Overheat

Schneider Altivar

Possible causes: Drive temperature too high,

Remedy: 

  • Check the motor load, the drive ventilation and the ambient temperature. 
  • Wait for the drive to cool down before restarting.

 

Code: F012 Process Overload.

Possible causes: Process overload.

Remedy: Check that drive parameters and application processes are compatible.

 


Code: F013 Motor Overload.

Schneider Altivar

Possible causes: Triggered by excessive motor current,

Remedy: Check configuration of motor thermal protection and motor load,

 


Code: F014 Output Phase Loss.

Possible causes: Loss of one phase on drive output.

Remedy:

  • Check the connections from the drive to the motor,
  • If using a downstream contactor, make sure the connection, cable and contactor are right.

 


Code: F015 Output Phases Loss.

Schneider Altivar

Possible causes:

  • Motor not connected,
  • Motor power too low, below 6% of the rated drive current,
  • Output contactor open,
  • Transient instability in the motor current,

Remedy:

  • Check the connections from the drive to the motor,
  • Test on a low power motor or without a motor. In factory settings mode, motor phase loss detection is active Output Phase loss detection.
  • To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive, deactivate motor phase loss detection Output Phase loss detection,
  • Check and optimize IR compensation, Rated motor voltage and then perform Auto-tuning,

 

Code: F016 Main Over-Voltage.

Schneider Altivar

Possible causes:

  • Line voltage too high: - At drive power on, supply is 10% over the maximum acceptable voltage level - At power with no run command, 20% over maximal line supply.
  • Disturbed mains supply.

Remedy: 

  • Turn Off the Drive. Check and adjust the line voltage. 
  • After line come back to nominal voltage (within tolerance) do power ON. 
  • If intermittent F016 code appear, set R1 assignment 205 to 01 and it can be connected to upstream protection to avoid overvoltage in the drive. 
  • In this case LO1 can be used for others drive status,

 

Code: F017 Input Phase Loss.

Possible causes:

  • Drive incorrectly supplied or a fuse blown,
  • Failure of one phase,
  • 3-phase ATV 310 used on a single-phase line supply,
  • Unbalanced load,
  • This protection only operates with the drive on load,

Remedy:

  • Check the power connection and the fuses,
  • Use a 3-phase line supply,
  • Disable reporting of this fault type by setting Input Phase loss detection,


Code: F018 Motor short-circuit and F019 Ground short-circuit,

Schneider Altivar

Possible causes:

  • Short-circuit or grounding at the drive output,
  • Ground fault while in run state,
  • Motor switching while in run state,
  • Significant current leakage to ground while several motors are connected in parallel,

 Remedy:

  • Verify the cables connecting the drive to the motor and the motor insulation,
  • Adjust the switching frequency,
  • Connect chokes in series with the motor,
  • Verify the adjustment of speed loop.


Note:

  • Fault detection codes which cannot be cleared automatically:
  • The cause of the detected fault must be removed before resetting by cycling power to the drive.