Danfoss VLT VFD Drive FC 301/302 Warnings and Alarms 1 to 10
In this Article we are going to see Danfoss VLT Drive FC 301/302 Warnings and Alarms 1 to 10.
WARNING-1: (10-Volts low)
- The control card voltage is less than 10 Volt from terminal 50.
- Remove some of the load from terminal 50, as the 10 Volt supply is overloaded.
- Maximum 15
mA or minimum 590 ohm.
- A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition.
- Remove the wiring from terminal 50,
- If the warning clears, the problem is with the wiring,
- If the warning does not clear, replace the control card.
WARNING/ALARM-2: (Live zero error)
- This
warning or alarm only appears if programmed by the user in parameter 6-01 Live Zero Timeout Function.
- The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input.
- Broken wiring or faulty device sending the signal can cause this condition.
Troubleshooting Methods:
- Check connections on all the analog input terminals,
- Control card terminals 53 and 54 for signals, terminal 55 common,
- VLT General Purpose
I/O MCB 101 terminals 11 and 12 for signals, terminal 10 common,
- VLT Analog I/O MCB 109
terminals 1, 3, 5 for signals, terminals 2, 4, 6 common,
- Check that the frequency converter programming and switch settings match the analog signal type,
- Perform Input Terminal Signal Test,
WARNING/ALARM-3: (No motor)
- No motor is connected to the output of the frequency converter.
WARNING/ALARM-4: (Mains phase loss)
- A phase is missing on the supply side, or the mains voltage imbalance is too high.
- This message also appears for a fault in the input rectifier.
- Options are
programmed in parameter 14-12 Response to Mains Imbalance.
Troubleshooting Methods:
- Check the supply voltage and supply currents to the frequency converter.
WARNING-5: (DC link voltage high)
- The DC-link
voltage is higher than the high-voltage warning limit.
- The limit
depends on the frequency converter voltage
rating.
- The unit is still active.
WARNING-6: (DC link voltage low)
- The DC-link voltage is lower than the low-voltage warning limit.
- The limit depends on the frequency converter voltage rating.
- The unit is still active.
WARNING/ALARM-7: (DC over voltage)
- If the DC-link voltage exceeds the limit, the frequency converter trips after some time.
Troubleshooting Methods:
- Connect a brake resistor.
- Extend the ramp time.
- Change the ramp type.
- Activate the functions in parameter 2-10 Brake Function.
- Increase parameter 14-26 Trip Delay at Inverter Fault.
WARNING/ALARM-8: (DC under voltage)
- If the DC-link voltage drops below the under voltage limit, the frequency converter checks if a 24 Volt DC back-up supply is connected.
- If no 24 Volt DC back-up supply is connected, the frequency converter trips after a fixed time delay.
- The time delay varies with unit size.
Troubleshooting Methods:
- Check that the supply voltage matches the frequency converter voltage.
- Perform an input voltage test.
- Perform a soft charge circuit test.
WARNING/ALARM-9: (Inverter overload)
- The frequency converter has run with more than 100% overload for too long and is about to cut out.
- The counter for electronic thermal inverter protection issues a warning at 98% and trips at 100% with an alarm.
- The frequency converter cannot be reset until the counter is below 90%.
Troubleshooting Methods:
- Compare the output current shown on the LCP with the frequency converter rated current and measured motor current
- Show the thermal frequency converter load on the LCP and monitor the value.
- When running above the frequency converter continuous current rating, the counter increases.
- When running below the frequency converter continuous current rating, the counter decreases.
WARNING/ALARM-10: (Motor Overload Temperature)
- According to the electronic thermal protection (ETR), the motor is too hot.
Select 1 of these options:
- The frequency converter issues a warning or an alarm when the counter is >90% if parameter 1-90 Motor Thermal Protection is set to warning options.
- The frequency converter trips when the counter reaches 100% if parameter 1-90 Motor Thermal Protection is set to trip options.
- The fault occurs when the motor runs with more than 100% overload for too long.
Troubleshooting Methods:
- Check for motor overheating.
- Check if the motor is mechanically overloaded.
- Check that the motor current set in parameter 1-24 Motor Current is correct.
- Ensure that
the motor data in parameters 1-20 to 1-25 is set correctly.
- If an
external fan is in use, check that it is selected in parameter 1-91 Motor External Fan.
- Running AMA
in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces thermal loading.
Video Link:
DANFOSS FC 51 VLT Micro drive Settings 1.Danfoss VFD Drive LCP SIMULATOR Tool Overview 2. DANFOSS VLT-6000 HVAC VFD Drive Basic Setting Parameter Part-1 3. DANFOSS INVERTER FC-301/302 Setting Parameters (Part-4) 4. DANFOSS INVERTER FC-301/302 Setting Parameters (Part-3) 5. DANFOSS INVERTER FC-301/302 Setting Parameters (Part-2) 6. DANFOSS INVERTER FC-301/302 Setting Parameters (Part-1) 7. Danfoss VLT VFD Drive FC 301/302 Warnings and Alarms 1-10 Part-1
Other Post Link:
Social Media Link:
Will i hope this Article is useful to you, thank you for Visiting our Blog, Have a great day.
Useful Information
ReplyDeleteNice
ReplyDeletegood effect
ReplyDelete